M6A4P 1*630/16

Description

Description

Standards

  • Product
    IEC 60502-2
  • Test
    IEC 60332-1-2

Application

Power use outdoor application, even wet.

Suitable for fixed installations at open air, in tube or canals and underground.

Max. Operation temperature: 90°

Max. Short circuit temperature : 250° (Max 5 s)

Construction

AL/SC/XLPE/SC/CU WIRES/PE

1. Conductor: Compacted Round conductor class 2

2. Insulation: Extruded inner semi conductive layer, XLPE insulation and  extruded outer semi conductive layer

3. Metallic screen layer: Copper wires with open helix copper tape

4. Outer sheath: PE FR

5. Marking: By Inkjet

6. Packing: Drums can be wooden or steel

TEST AT WORKS ACCORDING TO IEC 60502-2 / PRÓBY FABRYCZNE XnRUHAKXS, XnRUHKXS

Routine Tests / Badania rutynowe:

• Max. DC conductors resistance at 20°C acc. to IEC 60228 & IEC 60502-2 parag.16.2 / Maks. rezystancja DC żył w temperaturze 20°C zgodnie z IEC 60228 i IEC 60502-2 pkt 16.2

• High voltage test acc. to IEC 60502-2 parag. 16.4 / Próba wysokim napięciem zgodnie z IEC 60502-2 pkt 16.4

• Max. partial discharge test at 1.73 Uo acc. to IEC 60502-2 parag. 16.3 / Badanie maksymalnych wyładowań niezupełnych przy 1,73 Uo zgodnie z IEC 60502-2 pkt 16.3

 

Liban Cables will carry out these tests on all the lengths and tests certificates will be provided  / Firma Liban Cables przeprowadzi te badania dla wszystkich odcinków kabli i dostarczy świadectwa z badań

 

Sample tests / Badania próbek:

• Check of the build - up and color coding of the cable / Sprawdzenie rozwijania i kolorowych oznaczeń kabla

• Check of dimensions / Sprawdzenie wymiarów

Insulation / Izolacja        :           according to IEC 60502-2 / zgodnie z IEC 60502-2          Parag. / pkt.      17.5.2

Metallic screen / Ekran metaliczny          :           according to IEC 60502-2 / zgodnie z IEC 60502-2          Parag. / pkt.            17.7

Oversheath / Powłoka zewnętrzna           :           according to IEC 60502-2 / zgodnie z IEC 60502-2          Parag. / pkt.            17.5.3

- Hot Set Test for XLPE insulation according to IEC 60502-2 parag. 17.10 /-Badanie stopnia usieciowania izolacji z XLPE zgodnie z IEC 60502-2 pkt 17.10

 

These tests will be carried out on one length of each size during each inspection . / Badania te – podczas każdej kontroli – zostaną przeprowadzone na jednym odcinku dla każdego rozmiaru kabla.

Tests certificates will be provided by Liban Cables / Świadectwa z badań dostarczy firma Liban Cables

 

Type tests / Próby typu

Mechanical characteristics on insulation and sheaths material (tensile strength and elongation at break ) in accordance with IEC 60502-2. / Charakterystyki mechaniczne materiałów izolacji i powłoki zewnętrznej (wytrzymałość na rozciąganie i wydłużenie przy zerwaniu) zgodnie z IEC 60502-2.

These tests will be carried out on one length of the order / Badania te zostaną przeprowadzone na jednym odcinku z zamówienia

Tests certificates will be provided by Liban Cables / Świadectwa z badań dostarczy firma Liban Cables

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Aluminum
Conductor flexibility
Stranded class 2
Conductor shape
Circular compacted
Material of the inner semi-conductor
Semi-conducting compound
Insulation
XLPE
Material of the external semi-conductor
Extruded semiconducting compound - fully bonded
Concentric conductor
Copper wires and helical copper tape
Outer sheath
PE
Sheath colour
Black

Dimensional characteristics

Dimensional characteristics

Conductor cross-section
630 mm²
Conductor diameter
29.6 mm
Nominal insulation thickness
8.0 mm
Screen section
16 mm²
Nominal outer sheath thickness
2.7 mm
Nominal outer diameter
54.0 mm
Approximate net weight
3350 kg/km

Electrical characteristics

Electrical characteristics

Test voltage
63 kV
Rated Voltage Uo/U (Um)
18 / 30 (36) kV
Frequence
50 Hz
Perm current rating in air 30°C
916 A
Permissible current rating when buried
592 A
Max. DC resistance of the conductor at 20°C
0.0469 Ohm/km
A.C. Conductor resist. 50Hz and at 90 °C
0.0626 Ohm/km
Permissible short circuit current conductor 1s
60.2 kA
Thermal soil resistivity wet zone
1.5 °K.m/W

Mechanical characteristics

Mechanical characteristics

Cable flexibility
10xD
Mechanical resistance to impacts
Good

Usage characteristics

Usage characteristics

Flame retardant
IEC 60332-1-2
Operating temperature, range
-15 ... 55 °C
Bending factor when laying
20 (xD)
Laying depth, center of system
800 mm
Ambient air temperature
30 °C
Ambient ground temperature
20 °C
Max. conductor temperature in service
90 °C
Short-circuit max. conductor temperature
250 °C

Resources

Resources

Declaration of Performance

  • Declaration of Performance n� : 1001282-LBNI
  • Certification Date : 12/4/24
  • AVCP (Assessment and Verification of Constancy of Performance) : System 4
  • Declared performance : Fca

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close